Braided hose connections beneath a healthcare basin

Braided flexible hoses can raise Legionella risk in a commercial water system. The stainless steel braid is not the problem. The concern is the rubber or plastic lining underneath it, which can be colonised by bacteria, and the stagnant water that sits in hoses on rarely used outlets. If you manage a school, surgery, care setting or office, these hoses belong in your Legionella risk assessment, on your flushing schedule and on a planned replacement list. Our Legionella risk assessments start from £185 and record every flexible hose on site as part of the written assessment.



TL;DR

 

  • Most hoses sold for building services are EPDM rubber covered with a stainless steel braid, and the lining, not the braid, is what bacteria colonise.

  • HSE guidance tells healthcare premises to avoid EPDM-lined flexible hoses, and to use flexible connections only where equipment has to move or vibrate.

  • Infrequently used outlets, including those fed by hoses, need flushing weekly for several minutes, with each flush logged.

  • Rubber and plastic hose assemblies should be on a planned replacement cycle. The BSRIA code points to 10 years where there is no other evidence.

  • Check that any hose in contact with water is WRAS approved and tested to BS 6920.

 

Table of Contents

 

 

Why a braided hose is not a simple pipe

 

A flexible hose is a short, bendy connection between fixed pipework and a tap, valve, shower or appliance. You find them under basins, behind sinks, on tap tails, on shower fittings and on thermostatic mixing valve (TMV) assemblies. A TMV is a valve that blends hot and cold water to a safe outlet temperature.

 

The BSRIA Flexible Hose Code of Practice notes that most hoses sold for building services are EPDM rubber with a stainless steel braid, and that gradual thermal degradation of the rubber limits their life. The braid gives strength and stops the hose swelling under pressure. It does nothing to keep the water inside clean.

 

That is why a hose can look perfect from outside and still be a problem. The inner surface is rough compared with copper or stainless pipe, it is hidden, and nobody sees it when they walk the site.

 

How hoses increase Legionella risk

 

Legionella bacteria multiply in water between roughly 20°C and 45°C, feed on biofilm (the slimy layer microorganisms form on wet surfaces) and thrive where water does not move. Hoses can contribute to all three.

 

Lining materials that support biofilm

 

The HSE’s technical guidance, HSG274 Part 2 (2024), says that system design must identify components that may increase the risk of colonisation, and it names blending valves and flexible hoses as examples. The Approved Code of Practice L8 adds the underlying duty: water systems must avoid materials that harbour bacteria or provide nutrients for microbial growth.

 

In healthcare, the guidance is more specific. The Welsh version of HTM 04-01 reports high counts of Pseudomonas and Legionella in samples from outlets fed by flexible lined hoses, caused by colonisation of the lining. It also notes that EPDM may be susceptible to microbial colonisation.

 

The plumbing profession takes a similar view. The Chartered Institution of Plumbing and Heating Engineering says investigations have shown some flexible tap connectors are unsuitable because their inner surfaces let bacteria attach and form biofilm. It also says that contracting Legionnaires’ disease this way would be rare. For a duty holder, rare is not the same as ignorable: the law asks you to assess and control foreseeable risk.


Lining materials that support biofilm

Stagnation and low use

 

HSG274 Part 2 lists dead legs, capped pipes, infrequently used outlets and areas of poor circulation as places where stagnation and growth temperatures coincide. A hose on a basin nobody uses fits that description. So does a hose on a spare treatment-room tap, a staff kitchenette closed for refurbishment or a classroom sink that sits idle through the holidays.

 

The water in a hose is also in a warm place. Under-sink cold lines can pick up heat from nearby hot pipes and appliances, and the cold feed can drift above the 20°C ceiling. HSE advises storing and distributing cold water below 20°C, hot water stored above 60°C and distributed above 50°C.

 

Downstream of mixing valves

 

The Department of Health’s HTM 04-01 Part B notes that water quality can deteriorate in components such as terminal fittings, particularly when use is low. It adds that pipework downstream of thermostatic mixing valves may pose a particular problem because the lower temperatures can encourage growth of waterborne pathogens. Many flexible tails sit exactly there, between the TMV and the tap or shower.

 

What the guidance says you should do

 

Avoid them where you can

 

HSG274 Part 2 advises that healthcare premises should avoid EPDM-lined flexible hoses (often called tails), because they have been shown to be a risk of microbial colonisation. It says flexible connections should only be used where an installation has to move during operation or is subject to vibration.

 

The Welsh healthcare guidance goes further and restricts flexible hoses to three uses: allowing for equipment vibration, accommodating the vertical movement of height-adjustable baths and sinks, and enabling essential maintenance of bespoke equipment where no alternative exists. Where hoses are fitted, they should be as short as possible and free of kinks so flow is not affected.

 

In Scotland, SHTM 04-01 Part E allows flexible braided sections where space is limited, but requires alternatives to EPDM for the lining, citing a 2009 safety action notice.

 

Some organisations apply a stricter rule. One NHS ambulance trust’s water quality procedure from August 2024 bans flexible hoses for water connections and requires any found in existing buildings to be replaced with copper or steel pipework within 12 weeks. That is one trust’s policy, not a national rule, but it shows the direction of travel in regulated estates.

 

Choose compliant materials

 

HSG274 Part 2 says domestic water systems must not use materials that support microbial growth, such as natural rubber, and that fittings should comply with the WRAS approval scheme, with products tested to BS 6920. WRAS, the Water Regulations Advisory Scheme, approves products that are safe for contact with drinking water. The Welsh guidance lists newer lining materials such as PE, PEX, LLDPE and post-chlorinated PVC that should comply with BS 6920-1:2014.

 

In practice, this means a hose with no WRAS approval mark, or one bought on price from an unbranded source, is a risk you can remove cheaply at specification stage.

 

Flush infrequently used outlets

 

HSG274 Part 2 says weekly flushing of infrequently used outlets for several minutes can significantly reduce the risk of Legionella proliferation. The procedure must be sustained and logged, and high-risk settings such as healthcare and care homes may need it more often. The ambulance trust procedure above sets a minimum of three minutes per week for each hot and cold tap, recorded on site.

 

Flushing works on the hose as well as the tap, because the whole volume of water in the assembly is replaced. A missed week or a flush that nobody logged weakens your position if there is ever an incident.

 

Inspecting braided hoses: a practical routine

 

HSG274 Part 2 does not give a single “hose check” line, but its maintenance tables cover the same ground. Showers and spray taps, including hoses where fitted, are to be dismantled, cleaned and descaled quarterly, or as indicated by fouling rate or risk factors such as high-risk patients, with the inspection recorded. Cold-water sentinel taps (the ones furthest from and nearest to the tank) are checked monthly, with the cold water reaching below 20°C within two minutes of running. Thermal insulation is checked annually.

 

For hoses specifically, a sensible routine looks like this:

 

  1. Build a register. Walk the site and list every flexible hose: location, length, lining material if known, manufacturer, date stamp and whether it is WRAS approved. Hoses that comply with the BSRIA code are date stamped so replacements can be tracked.

  2. Rank by risk. Hoses serving vulnerable people (patients, children, residents), shower hoses, hoses downstream of TMVs and hoses on low-use outlets come first.

  3. Look and feel. Check for kinks, bulging, corrosion or broken braid strands, leaks at the ferrules and fittings, and a damp or slimy feel at the connection.

  4. Take temperatures. Record the cold and hot temperatures at the outlet, not only at the tank or plant room. A cold line drifting above 20°C needs investigating.

  5. Flush and log. Put every low-use outlet on the weekly schedule and record who did it and when.

  6. Act on findings. Clean and descale, disinfect, remove or replace. Re-sample if the outlet has previously failed.

 

Where a result is out of range, water sampling from the outlet shows whether the hose is contributing. Our Legionella testing and analysis service starts from £55 per sample, and covers Pseudomonas aeruginosa and total viable count testing as well as Legionella.

 

How long should a braided hose stay in service?

 

There is no statutory expiry date, but there is a widely used benchmark. The BSRIA code of practice says rubber and plastic hose assemblies that meet the HMSA standard (the Hose Manufacturers and Suppliers Association standard) are expected to last at least 10 years when properly specified and installed. Metal hoses are given 25 years. In the absence of other evidence, it recommends that building owners consider planned replacement of rubber and plastic hoses every 10 years, adjusted according to sampling and examination.

 

Two practical points follow. First, 10 years is a ceiling for a correctly specified hose in normal conditions, not a guarantee. A hose that has been kinked, overheated or tested positive for bacteria should come out sooner. Second, the interval only works if you know how old the hose is. Without a register and date stamps, you cannot prove a replacement cycle exists, which is what an auditor or investigator will ask for. We cover the schedule side in more detail in our guide to a flexible hose replacement schedule.

 

Situation

Typical action

EPDM-lined hose in healthcare premises

Remove, or replace with a compliant alternative lining or rigid pipework

Hose serving a rarely used outlet

Weekly flush, logged; consider removing the outlet or hose

Hose downstream of a TMV

Include in temperature checks and TMV servicing; keep as short as possible

Shower hose

Clean and descale at least quarterly; replace if damaged or scaled

Hose with no markings or approval

Replace with a WRAS-approved, date-stamped assembly

Hose over 10 years old, rubber or plastic

Replace unless sampling and inspection support keeping it

Where hoses fit in a school, surgery or office

 

The same hose can mean different levels of risk depending on who uses the water.

 

  • Schools and colleges: long holidays leave outlets idle for weeks. Hoses behind classroom and science-room sinks, and on changing-room showers, need flushing on return and a regular schedule in term time.

  • Doctors’ and dental surgeries: clinical handwash basins often use mixer taps with flexible tails, and dental units have their own water lines. Patients may be vulnerable, so the stricter healthcare approach is the safer reference. See our page on Legionella compliance for healthcare premises.

  • Offices and facilities-managed buildings: kitchenettes, showers for cyclists and little-used washrooms are typical weak points. Our guide to types of water outlets and their Legionella risk helps you rank them.

  • Housing associations: void properties and communal areas leave hoses unused for long periods. See Legionella prevention in social housing.

 

Our perspective

 

Hoses are the item we most often see left off a site’s records, because they are hidden, cheap and fitted by whoever was last on the job. The register is where compliance starts. If you do not know what is behind the panel, you cannot flush it, sample it or replace it on time.   Our approach to a Legionella risk assessment is to look at each site as it is, not to apply a template. That means the flexible hoses, the TMVs and the low-use outlets get named in the report, with actions you can put in a logbook and work through.   The strongest position for a duty holder is a simple one: fewer flexible hoses, compliant ones where they are needed, a dated replacement plan, and flushing that is logged every week. Temperature monitoring, servicing and remedial works then keep that position in place between assessments.   Sammi

 

Getting hoses under control

 

If your hose register does not exist yet, the quickest way to build one is through a site risk assessment. Our Legionella risk assessments start from £185 and are tailored to each site, with a bespoke logbook system and an ongoing support option for the actions that follow.

 

[


Bespokecompliancesolutions

 

For the work that follows, we offer TMV servicing and general remedial works, system disinfection and cold water tank work, and automated water temperature monitoring to catch cold lines drifting out of range. We also run Legionella awareness training on site or online, so the people doing the weekly flush know what they are looking for.

 

FAQ

 

Are braided hoses banned in UK buildings?

 

No general ban applies to all buildings. HSG274 Part 2 advises healthcare premises to avoid EPDM-lined flexible hoses and to use flexible connections only where movement or vibration requires it. Individual organisations, including some NHS trusts, set stricter policies.

 

Does the stainless steel braid stop Legionella growing?

 

No. The braid protects the hose from pressure and wear. Bacterial colonisation happens on the inner lining, which is commonly EPDM rubber in building-services hoses.

 

How often should flexible hoses be replaced?

 

The BSRIA code of practice suggests considering planned replacement of rubber and plastic hose assemblies every 10 years where there is no other evidence, adjusted by examination and sampling. Replace sooner if a hose is damaged, scaled or linked to a failed sample.

 

How often should I flush outlets fed by hoses?

 

HSG274 Part 2 says infrequently used outlets should be flushed weekly for several minutes, with the flushing sustained and logged. Higher-risk settings such as healthcare and care homes may need it more often, as your risk assessment indicates.

 

Is a braided hose safe for drinking water?

 

Only if it is suitable for contact with drinking water. HSG274 Part 2 says fittings and components should comply with the WRAS approval scheme, with products tested to BS 6920, and that materials supporting microbial growth must not be used.

 

Sources

 

Recommended

 

 
 
 

Comments


bottom of page