Water Hygiene Record Keeping in the UK: What to Log and for How Long

If you are responsible for a building’s water system in England, your records are your evidence. They must show who is responsible, what the risk assessment found, what you did about it and what the checks and tests showed. Keep monitoring results for at least five years, and keep the risk assessment and written scheme for as long as they are current plus two more years. Every entry should be dated and signed, on paper or electronically. We build and maintain these logbooks for organisations across the UK, and the rest of this guide sets out exactly what the official guidance expects.
TL;DR
Dutyholders with five or more employees must record the risk assessment’s significant findings, the written scheme and its implementation, the state of each system and the results and dates of every check, test and inspection.
Risk assessment and written scheme records are kept while current and for at least two years afterwards. Monitoring, inspection, test and check records are kept for at least five years.
Records can be written or electronic, but each entry must show who did the work and when, and be signed, verified or otherwise authenticated.
Failed checks only count as managed when the corrective action, its completion date and the person responsible are in the same log.
Care homes and oral health services applying to the Care Quality Commission (CQC) need a current Legionella risk assessment with supporting records.
Table of Contents
What the law expects you to record
The Health and Safety Executive (HSE) sets out the record-keeping duty in its Approved Code of Practice, known as L8. An Approved Code of Practice is guidance with special legal status: if you are prosecuted for a breach and have not followed it, you must show you complied with the law in some other way. L8 is supported by technical guidance called HSG274, which describes the practical checks.
Who has to write things down
Under HSE’s L8 Approved Code of Practice, employers with five or more employees must record the significant findings of their Legionella risk assessment, along with the other items listed below. With fewer than five employees there is no statutory duty to write anything down, though a written record is still useful. In practice, most schools, surgeries, offices and care settings are well over that threshold, and anyone who inherits a building, changes contractor or faces an inspection will want the paper trail regardless of headcount.
The core records
HSE’s L8 guidance asks you to keep a record of:
the person or people responsible for carrying out the risk assessment and for managing the written scheme;
the significant findings of the risk assessment;
the written scheme (the plan of precautions and checks for each system) and how it is being implemented;
the state of operation of the system, in other words whether it is in use or not in use;
the results and dates of any monitoring, inspection, test or check carried out.
The fuller L8 list goes further. It includes schematic diagrams of the system, precautionary measures with dates, remedial work required and carried out, a log of contractor and consultant visits, cleaning and disinfection procedures with their reports and certificates, chemical and biological monitoring results, training records, the lines of communication for the responsible people, and signatures or other authentication of the work.
If your written scheme is out of date or never properly written down, start there. Our guide to what a Legionella written scheme must contain explains the document that most other records hang from.
A practical way to group them
Most facilities teams find it easier to think of the records in four groups:
Group | What it holds | Typical owner |
Governance | Named responsible person, deputy, lines of communication, competence and training records | Compliance or estates manager |
Assessment | Risk assessment, significant findings, system schematics, review dates | Competent assessor and responsible person |
Control | Written scheme, flushing, temperature checks, cleaning and disinfection, TMV servicing | Site maintenance team or contractor |
Evidence | Sample results, certificates, remedial work, contractor visit log | Responsible person |
The benefit of grouping is that a gap shows up quickly. If the Control group is full and the Governance group is empty, an inspector will notice before you do.
How long to keep each record
Retention is the part people most often get wrong, usually by throwing out older monitoring sheets when a new risk assessment arrives. The rules in HSG274 Part 2 are simple: records are retained while current and for at least two years afterwards, except monitoring and inspection records, which should be kept for at least five years. HSE’s guide for dutyholders, INDG458, gives the same periods.
Record | Minimum retention |
Risk assessment and significant findings | While current, plus at least 2 years |
Written scheme and its implementation | While current, plus at least 2 years |
Monitoring, inspection, test and check results | At least 5 years |
Training records, external service provider records, other hazard information | Helpful to keep, no fixed period in HSG274 |
Two practical points follow.
Count from the right date. For a risk assessment, the clock starts when it is replaced, not when it was written. A 2021 assessment superseded in 2025 should be kept until at least 2027.
Keep the rolling window complete. Because monitoring records must cover five years, a site audited in 2026 should be able to produce results back to 2021. A missing winter is as noticeable as a missing year.
Some healthcare bodies set longer internal periods. One Scottish health board, for example, keeps electronic records for ten years or more. If you work under an NHS trust’s or local authority’s own policy, follow whichever period is longer.

Which routine checks belong in the log
The regulations do not hand you one universal schedule. Frequencies depend on the system’s design, use and risk, and the written scheme sets them. What is consistent is that every check carried out must be logged with its date and result. Typical entries include:
hot and cold water outlet temperatures, taken on a rotating sample of outlets;
storage and return temperatures at calorifiers (hot water cylinders);
cold water tank inspections and temperatures;
flushing of little-used outlets, showers and infrequently used rooms;
shower head and hose cleaning or descaling;
thermostatic mixing valve (TMV) servicing and outlet temperatures;
water sample results and any action taken;
the state of the system: in use, shut down or mothballed.
If you want the temperature thresholds themselves, our note on HSG274 temperature limits for England dutyholders covers the 60°C storage and 50°C outlet figures. For the day-to-day routine, our temperature monitoring checklist and the walkthrough on how to complete temperature monitoring checks show what to measure and how to write it down.
NHS facilities teams often go further and log monthly, six-monthly and annual distribution checks against a task-by-task schedule, with the responsible person informed immediately of any result outside limits. You do not need that depth in a small office, but the principle scales: a schedule that says what is checked, how often and where the result is recorded.
Do not forget the quiet entries
Negative or routine results matter as much as failures. A line that says “outlets 1 to 12 checked, all within limits, 14 March” is evidence of control. A blank row is evidence of nothing. Likewise, record when a building or wing is closed or part-used, because stagnation risk rises when a system is not in use. The “state of operation” entry in L8 exists precisely for this.
Making every entry auditable
An auditor, insurer or inspector will ask three things of any record: who did it, when, and what happened next. HSG274 says records should contain accurate information about who did the work and when it was carried out, and should be signed, verified or authenticated by a signature or other appropriate means.
Scottish healthcare guidance, SHTM 04-01, is a useful model for any sector. It says the individual concerned should sign and date entries and that an audit trail should be in place. Applying that to a typical site gives these habits:
One name per entry. Initials alone are weak if three people share them. Use a signature list at the front of the logbook.
Record the reading, not just “OK”. Write the temperature, the outlet reference and the thermometer used.
Log the failure and the fix together. If an outlet misses its limit, note the date, who was told, the corrective action, the completion date and the re-check result.
Record remedial work against the risk assessment. L8 asks for remedial work required and carried out, with dates, so close each action in the log.
File certificates beside the entry. Cleaning and disinfection reports, sample certificates and TMV service sheets should be referenced at the point the work occurred.
Record training. Keep who was trained, on what and when, for the responsible person, deputies and anyone carrying out checks.
Date the review. Note when the risk assessment was last reviewed and what triggered the review. Our guide to reviewing a Legionella risk assessment explains when that should happen.
A useful self-test is to pick any outlet at random and trace its history through the log for the last 12 months. If you can follow it without asking anyone, the system works. If you have to ask who “JB” is or where the sample certificate went, it needs fixing.
Paper or electronic: both are acceptable
HSG274 is clear that records can be written or electronic. What matters is accuracy, attribution and authentication. A spreadsheet that anyone can overwrite without a trace is weaker than a bound logbook with signed entries, while a system with user log-ins, time stamps and locked past entries is stronger than both.
When you move to electronic records, check the following:
every entry carries the user’s name and a time stamp that cannot be edited afterwards;
corrections are added as new entries rather than overwriting the old ones;
backups exist and you can export the full five-year history on request;
staff who sign electronically understand that it carries the same weight as a handwritten signature. For a plain-English look at the principles, see these electronic signatures in healthcare compliance checks.
For temperature data in particular, automated water temperature monitoring takes readings continuously and stores them without anyone writing a figure down, which removes the commonest record-keeping weakness: a missed or backfilled manual entry. It does not replace the rest of the logbook, but it makes the temperature section of it far harder to dispute.
Healthcare, care homes and dental settings
If you run a GP surgery, dental practice, care home or other regulated setting, your records are read by a second audience as well as HSE. HSG274 notes that water systems in healthcare premises, care homes and residential homes need particular consideration in the risk assessment.
In England, the Care Quality Commission asks care homes and oral health services applying for registration to provide a current Legionella risk assessment, and from 17 August 2026 it also asks this of ambulance services. CQC says the assessment should include system mapping, maintenance logs, temperature monitoring records, cleaning and disinfection schedules and remedial action plans. In other words, a provider’s logbook is part of the registration evidence, not an afterthought.
In dental surgeries the practical risk is dental unit waterlines and little-used taps, so flushing and any local disinfection should be logged with the same discipline as temperatures. In schools and colleges, the usual gaps are holiday closures and little-used outlets: log the closure, the flush on return and the result. For offices and other commercial premises, our guide to Legionella compliance in offices and commercial premises covers what is typically in scope.

A record-keeping routine you can run from this week
Here is a routine that fits most multi-site estates, with where we take work off your hands.
Name the people. Record the responsible person, deputy and the competent assessor. Where we carry out the assessment, the named assessor and date appear on the report itself.
Get a current risk assessment. Without it, no log has anything to refer to. Our Legionella risk assessments start from £185 and are bespoke to each site.
Turn the findings into a written scheme. List every system, check, frequency and who does it.
Set up one logbook per site. We implement a bespoke Legionella logbook system so that the sections match your written scheme, rather than a generic template.
Train the people who write in it. Our Legionella awareness training is available on site or online, and attendance goes into the training record.
Log samples and certificates as they arrive. Water sampling from £55 per sample is described on our Legionella water testing page.
Close every action. Remedial work, TMV servicing and disinfection each get a dated entry and a certificate or report.
Review monthly, audit annually. The responsible person signs a monthly review line and an annual audit checks five years of history.
Where we can help
We are a water hygiene and Legionella compliance business working with commercial, healthcare, education, housing and hospitality organisations across the UK. Our services are designed to make compliance simple: risk assessments, water sampling and analysis, awareness training, implementation of a control programme and a bespoke logbook system, plus ongoing consultancy. We produce comprehensive documentation so that the records an inspector asks for are in one place.
If you would like a second pair of eyes on your current records, or a logbook built around your sites, start with our Legionella compliance services or contact us through our website.
[

Our view: records are the control, not the paperwork after it
Many dutyholders think of the logbook as admin that follows the real work. We see it the other way round. A flush, a temperature reading or a sample result only counts as control once it is written down, dated and signed by the person who did it. That is why we build logbooks around each site’s own written scheme rather than handing over a generic template. The sections match the checks, the frequencies match the risk assessment and every entry has a place for the action that follows. Our training is there so the people filling in the book understand why each line matters, and our water sampling and remedial work feed straight into the same record. Where readings are taken often and missed readings carry real risk, we recommend automated temperature monitoring alongside the logbook. It keeps the temperature record continuous, and your team can spend its time on the checks that need a person. Our aim is simple: when someone asks for your records, you can hand them over without a scramble. Sammi
FAQ
Do I need a Legionella logbook if I have fewer than five employees?
There is no statutory duty to write down the significant findings if you employ fewer than five people. A written record is still useful, because it shows what you checked and when, and it helps any future manager, landlord or insurer. Most small sites keep a simple logbook anyway.
How long should water hygiene records be kept?
HSE guidance says risk assessment and written scheme records should be kept while current and for at least two years afterwards. Monitoring, inspection, test and check results should be kept for at least five years. If your organisation or regulator sets a longer period, follow that.
Can I keep water hygiene records electronically?
Yes. HSG274 accepts written or electronic records, as long as they accurately show who did the work and when, and are signed, verified or otherwise authenticated. Choose a system that locks past entries and records corrections as new entries.
Who should sign the entries?
The person who actually carried out the task should sign and date their own entry, with a signature list kept at the front of the logbook. The responsible person then reviews and countersigns at the intervals set in your written scheme.
What records will CQC expect from a care home or dental practice?
When applying for registration, care homes and oral health services need a current Legionella risk assessment. CQC says it should include system mapping, maintenance logs, temperature monitoring records, cleaning and disinfection schedules and remedial action plans.